dc.description.abstract | Analysis of the electrical protection system of IPR Pharmaceuticals This study is based on the electrical distribution system of a pharmaceutical plant. The purpose of the study is to investigate why the low voltage switchgear 800A circuit breaker feeding a motor control center (MCC) tripped to clear a fault that occurred at a 277V street light pole. We also want to know why the preceding 20A branch circuit breaker and the 60A main breaker feeding the panel board did not trip. As a consequence of this fault the steam boiler was shut down.The one-line diagran of the electrical system of the plant and the circuit breakers sequence connections are shown. To verify the existing coordination problem we plotted the time-current characteristic curves of die circuit breakers involved and made sure there was no overlapping between the breaker's curves. An overlapping means that either breaker or all of them will trip at the same time when a fault occurs. After studying and analyzing die fault we suggest two alternatives to solve this breaker coordination problem: changing the settings of the breakers to their maximum, and to replace one breaker for another with the ground fault protection option; however, we would have to change settings to the remainder breakers. | en_US |
dc.identifier.citation | Flores Nieves, R. H. & Pérez Dumeng, L. A. (1994). Análisis del sistema de protección de IPR Pharmaceuticals, Inc, Revista de la Universidad Politécnica de Puerto Rico, 4(2), 191-221. | en_US |
dc.identifier.uri | http://hdl.handle.net/20.500.12475/1473 | |
dc.language.iso | es | en_US |
dc.publisher | Polytechnic University of Puerto Rico | en_US |
dc.relation.haspart | San Juan | en_US |
dc.relation.ispartof | Revista de la Universidad Politécnica de Puerto Rico; | |
dc.rights.holder | Esta Junta Editorial y la Universidad Politécnica de Puerto Rico hacen constar y reconoce que los autores de los artículos, obras literarias y artísticas publicadas en esta Revista Politechnê, se reservan enteramente los derechos de autor y de publicación de los mismos para los efectos de cualquier ventualidad literaria, publicitaria o de cualquier índole. | en_US |
dc.rights.license | All rights reserved | en_US |
dc.subject.lcsh | Electric power systems--Protection | en_US |
dc.subject.lcsh | Polytechnic University of Puerto Rico--Undergraduates--Research | en_US |
dc.title | Análisis del sistema de protección de IPR Pharmaceuticals, Inc | en_US |
dc.type | Article | en_US |
Files
Original bundle
1 - 1 of 1
Loading...
- Name:
- PUPR_SJU_CEAH_Publicaciones_Revista UPPR_Vol04_Num02_Diciembre 1994_P191_Ramón H. Flores Nieves_Luis A. Pérez Dumeng_Article.pdf
- Size:
- 7.99 MB
- Format:
- Adobe Portable Document Format
- Description:
- PUPR_SJU_CEAH_Publicaciones_Revista UPPR_Vol04_Num02_Diciembre 1994_P191_Ramón H. Flores Nieves_Luis A. Pérez Dumeng_Article
License bundle
1 - 1 of 1
Loading...
- Name:
- license.txt
- Size:
- 1.63 KB
- Format:
- Item-specific license agreed upon to submission
- Description: