Retrofit Heat-Recovery Ventilation for an Office Building with Exhaust Heat Recovery

dc.contributor.advisorCruzado Vélez, Héctor J.
dc.contributor.authorColón Espinosa, Luis J.
dc.date.accessioned2026-07-01T17:14:06Z
dc.date.issued2026
dc.descriptionGraduate Project Poster for the Graduate Programs at the Polytechnic University of Puerto Rico summarizing graduate research through concise text and visuals.
dc.description.abstractThis study evaluated a retrofit heat recovery ventilation (HRV) system for a 70,000 ft², seven-story office building to reduce ventilation-related heating energy, improve indoor air quality (IAQ), and integrate with existing HVAC controls while minimizing disruption. A compact plate-type HRV with CO₂-based demand controls was selected. Phased installation and commissioning included test and balance procedures, control interlocks with the rooftop unit, and staff training. Twelve-month monitoring with 15-minute logging of energy and IAQ metrics showed a mean sensible heat-exchanger effectiveness of 72%, an 18% annual reduction in ventilation-related space-heating energy, and a reduction in occupied-hour CO₂ peak concentrations from values exceeding 1,200 ppm to sustained levels below 950 ppm. Integrated controls prevented overventilation and maintained occupant comfort. The estimated simple payback period ranged from 5 to 7 years. The retrofit demonstrated that a compact, well-commissioned HRV with demand control delivered measurable energy, IAQ, and operational benefits for midrise office buildings.
dc.identifier.citationColón Espinosa, L. J. (2026). Retrofit Heat-Recovery Ventilation for an Office Building with Exhaust Heat Recovery [Graduate project poster]. Graduate School, Polytechnic University of Puerto Rico. Puerto Rico Cloud Repository (PRCR). https://hdl.handle.net/20.500.12475/3349
dc.identifier.urihttps://hdl.handle.net/20.500.12475/3349
dc.language.isoen
dc.provenanceAcademic work generated by master’s students from the Graduate School of the Polytechnic University of Puerto Rico and preserved for access and dissemination through the Institutional Digital Repository.
dc.publisherPolytechnic University of Puerto Rico
dc.relation.ispartofArchivo Histórico de la Universidad Politécnica de Puerto Rico: Fondo Documental y Fotográfico
dc.relation.ispartofseriesVice Presidency of Innovation in Academic Affairs
dc.relation.ispartofseriesGraduate School
dc.relation.ispartofseriesArtículos de cursos de proyectos a nivel graduado
dc.relation.ispartofseriesEngineering Management Program
dc.relation.ispartofseriesSpring-2026
dc.rights.holderPolytechnic University of Puerto Rico, Graduate School
dc.rights.licenseAll rights reserved
dc.sourceUniversidad Politécnica de Puerto Rico. Biblioteca. Colecciones Especiales y Archivo Histórico
dc.subjectDemand controlled ventilation (CO2 based)
dc.subjectRetrofit commissioning
dc.subjectSensible heat exchanger effectiveness
dc.subjectVentilation related energy savings
dc.subject.lcshOffice buildings--Heating and ventilation
dc.subject.lcshBuildings--Energy conservation
dc.subject.lcshHeat exchangers
dc.subject.lcshVentilation--Automatic control
dc.subject.otherPolytechnic University of Puerto Rico--Graduate students--Posters
dc.titleRetrofit Heat-Recovery Ventilation for an Office Building with Exhaust Heat Recovery
dc.typePoster

Files

Original bundle

Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
PUPR_CEAH_SJU_SP26_MEM_Luis Colon_Poster.pdf
Size:
403.33 KB
Format:
Adobe Portable Document Format

License bundle

Now showing 1 - 1 of 1
License Image
Name:
license.txt
Size:
1.71 KB
Format:
Item-specific license agreed upon to submission
Description:

Collections